All Categories

Get in touch

Products

KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System
KOMAY Dense Copper/Aluminum Bus Duct System

KOMAY Dense Copper/Aluminum Bus Duct System

The dense busbar trunking system is a high-density insulated and compact power distribution equipment, widely used in high-current and high-reliability power transmission systems.

1. It adopts high-purity copper or aluminum busbars (conductivity ≥ 98%), with a rated current ranging from 250A to 6300A, meeting the requirements of large-capacity power distribution.

2. It features a low-loss design, with energy-saving efficiency 10% to 20% higher than traditional cables.

3. It has a standard protection level of IP54 (dustproof and splash-proof), and some models can reach IP65/IP66 (water-spray-proof and dust-proof), suitable for harsh environments such as dampness and dust.

4. It can be installed horizontally, vertically or at an angle, supporting long-span installation (horizontal support spacing ≤ 2.5 meters, vertical ≤ 3.6 meters), adapting to different power distribution needs. There are no exposed live parts, preventing the risk of electric shock.

  • Product Description
  • Application
  • Related product
  • Inquiry
Description
Implementation Standard IEC/EN 60 439-6, GB7251.1
System Three-phase three-wire, Three-phase four-wire, Three-phase five-wire (with separate PE busbar), Three-phase five-wire (with casingas PE)
Ambient Temperature -25/+40/+35 (Outdoor Type -40/+40/+35)
  Relative Humidity  No more than 50% at a maximum temperature of 40℃,and no more than 90% at 20℃.
 Ingress Protection (IP) Rating IP54, IP66, IP68  
 Rated Insulation Voltage (Ui) AC/ DC 1000V/800V
Rated Operating Voltage (Ue) AC1000V/690V
 Rated Frequency 50/60Hz
 Enclosure Material/Surface Treatment  Aluminum Alloy / Powder Coating
 Conductor Material Tin-Plated Copper or/Tin-Plated Copper-Clad Aluminum/Aluminum
 Voltage Category / Pollution Degree III/3

Copper Busbar System Parameter Table

Current Short-time withstand current (ICW)KA Peak withstand current (IPK)KA Resistance/m (MΩ) Reactance/m (MΩ) Impedance/m (MΩ) Voltage drop/m (V) Overall dimensions Width(W)Height(H) Weight/m (kg/m) 4-wire system 5-wire system
400 30   63 0.110 0.039 0.116 0.08 128 105 11.8 12.6
630 0.084 0.035 0.101 0.11 128 120 12.9 13.8
800 0.073 0.031 0.079 0.11 128 135 15.0 16.2
1000 50 105 0.060 0.028 0.086 0.18 128 155 17.2 18.7
1250 0.047 0.024 0.053 0.11 128 185 20.7 22.5
1600 65 143 0.033 0.020 0.039 0.11 128 225 27.6 30.2
2000 0.024 0.017 0.030 0.10 128 265 35.6 39.2
2500 0.018 0.014 0.023 0.10 128 335 45.9 50.7
3150 100 220 0.015 0.012 0.019 0.10 128 415 60.2 66.1
4000 0.011 0.009 0.014 0.10 128 525 76.3 84.0
5000 0.009 0.006 0.011 0.09 128 795 97.0 107.1
6300 120 264 0.007 0.004 0.008 0.09 128 655 124.5 127.6

Aluminum Busbar System Parameter Table

Current

Short-time withstand current (ICW)KA

Peak withstand current (IPK)KA

Resistance/m (MΩ)

Reactance/m (MΩ)

Impedance/m (MΩ)

Voltage drop/m (V)

Overall dimensions

Width(W)Height(H)

Weight/m (kg/m)

4-wire system 5-wire system

400

30

 

63

0.130

0.029

0.133

0.09

128

110

8.6

9.0

630

 

 

0.118

0.028

0.121

0.13

128

135

9.0

9.5

800

 

 

0.093

0.024

0.096

0.13

128

155

10.2

10.8

1000

50

105

0.065

0.020

0.068

0.12

128

175

12.7

13.5

1260

 

 

0.048

0.017

0.051

0.11

128

205

15.5

15.5

1600

 

 

0.036

0.014

0.039

0.11

128

245

19.2

20.6

2000

65

143

0.029

0.012

0.030

0.11

128

275

27.5

29.2

2500

 

 

0.022

0.009

0.024

0.10

128

315

33.1

35.5

3150

100

220

0.017

0.006

0.018

0.10

128

455

40.4

43.5

4000

 

 

0.013

0.004

0.013

0.09

128

545

46.9

54.2

Application